Analysis and Improvement Measures of Acetylene Gas in Converter Transformer

5 Pages Posted: 26 May 2023

See all articles by Qu Wentao

Qu Wentao

Pak Matiari Lahore Transmission Company Private Ltd.

Zhao Hang

Pak Matiari Lahore Transmission Company Private Ltd.

Muhammad Ubaid ur Rehman

PMLTC

Date Written: May 16, 2023

Abstract

After ± 660kV converter station put into operation, Acetylene gas was reported in the online oil chromatography of converter transformer. After half year of operation, the acetylene content of the converter transformer was 1.31ppm. It was exceeded the alarm value of 1ppm. The excessive acetylene gas in the oil interferes with the operation state analysis of the converter transformer. By analyzing the gas production mechanism of the tap changer switch, it is found that the polar switch produce acetylene gas. After the actual tracking verification, it is found that reducing the tap changer polar switch action could effectively reduce the acetylene content. This paper proposes the influence of tap changer switch on acetylene content and countermeasures to provide reference for the operation analysis of converter transformer.

Keywords: Converter Transformer, Acetylene, Tap Changer Switch, Online Monitoring

Suggested Citation

Wentao, Qu and Hang, Zhao and Rehman, Muhammad Ubaid ur, Analysis and Improvement Measures of Acetylene Gas in Converter Transformer (May 16, 2023). Available at SSRN: https://ssrn.com/abstract=4449555 or http://dx.doi.org/10.2139/ssrn.4449555

Qu Wentao

Pak Matiari Lahore Transmission Company Private Ltd.

Zhao Hang

Pak Matiari Lahore Transmission Company Private Ltd.

Muhammad Ubaid ur Rehman (Contact Author)

PMLTC ( email )

581-Z Phase#2 Stree#17 DHA Lahore
Lahore, PA Punjab 54000
Pakistan

Do you have a job opening that you would like to promote on SSRN?

Paper statistics

Downloads
21
Abstract Views
120
PlumX Metrics