Optimization Control Strategy for Mixed-Mode Buildings Based on Thermal Comfort Model: A Case Study of Office Buildings in Xi'An, China

33 Pages Posted: 29 Oct 2023

See all articles by Ying Yu

Ying Yu

affiliation not provided to SSRN

Tianhui Xiang

affiliation not provided to SSRN

Di Wang

affiliation not provided to SSRN

Liu Yang

Xi’an University of Architecture and Technology

Abstract

Mixed-mode (MM) buildings reduce air conditioning (AC) energy consumption while maintaining indoor thermal comfort through the appropriate use of natural ventilation (NV). The objective of this investigation was to propose a method to determine the best NV operation range suitable for MM buildings and further to propose a change-over control strategy. First, the usual natural ventilation operating range (NV-range) was obtained based on the upper and lower comfort temperature limits of the adaptive comfort model. The usual NV-range was extended by adding threshold conditions, and then, it was divided into nine natural ventilation operation subranges (NVOSs). Second, the comfort and energy performance of each NVOS were analyzed through a co-simulation for an MM office building in Xi'an, China, as an example to obtain the optimal NV-range for the local climate. The results showed that the proposed optimal NV-range reduced the number of discomfort hours by 248.33h while increasing the energy savings by 13.29% compared to those of the commonly used NV-ranges. Finally, the control scheme with the adaptive comfort model changed to the PMV model (ACM-PMV-CS) with the addition of a 1.5-h transition period was proposed in order to solve the problem of using the steady-state PMV model directly in the AC mode under the frequent switching conditions between the NV and AC modes. The results showed that ACM-PMV-1.5h transition period resulted in a reduction in the number of discomfort hours (248.33h) and a 35.46% increase in the energy savings compared to those of ACM-PMV-CS without a transition period.

Keywords: Mixed-mode buildings, Thermal comfort, Natural ventilation, Adaptive comfort model, PMV model

Suggested Citation

Yu, Ying and Xiang, Tianhui and Wang, Di and Yang, Liu, Optimization Control Strategy for Mixed-Mode Buildings Based on Thermal Comfort Model: A Case Study of Office Buildings in Xi'An, China. Available at SSRN: https://ssrn.com/abstract=4616305 or http://dx.doi.org/10.2139/ssrn.4616305

Ying Yu (Contact Author)

affiliation not provided to SSRN ( email )

No Address Available

Tianhui Xiang

affiliation not provided to SSRN ( email )

No Address Available

Di Wang

affiliation not provided to SSRN ( email )

No Address Available

Liu Yang

Xi’an University of Architecture and Technology ( email )

Do you have a job opening that you would like to promote on SSRN?

Paper statistics

Downloads
29
Abstract Views
137
PlumX Metrics